What is a PCC Panel?

A Power Control Centre (PCC) is the main distribution switchboard for an LV (low voltage) system. It receives power from the transformer secondary or from a DG set and distributes it to downstream feeders — typically MCCs, sub-distribution boards, and large individual loads.

A PCC handles the highest fault levels in the LV system. It is typically rated from 630A to 4000A or higher, and is built as a Form 3b or Form 4 assembly to IS 8623 / IEC 61439-1 & 2. Its busbars are sized for the full incoming current, and all outgoing feeders are protected by ACBs (Air Circuit Breakers) or MCCBs of appropriate rating.

The PCC's primary job is power distribution and protection — not direct motor or load control. You will not normally find contactors or overload relays inside a PCC. Its outgoing feeders go to panels that do the control work.

What is an MCC Panel?

A Motor Control Centre (MCC) is a centralised assembly of motor starter units. Each unit typically contains an isolator, fuses or MCCB, a contactor, and a thermal overload relay (or electronic motor protection relay). The MCC receives its supply from the PCC or from a sub-distribution board.

MCCs are designed around IEC 60947-4-1 (contactors and motor starters) and are built to Form 3b or Form 4 construction. Each motor feeder is a self-contained functional unit — faulted or under-maintenance units can be isolated without de-energising the whole panel.

An MCC may also include PLCs, soft starters, variable frequency drives (VFDs), and automation I/O for process control. In this configuration it is often called an Intelligent MCC or IMCC.

Key Differences at a Glance

Parameter PCC MCC
Primary function Power distribution Motor starting and control
Typical incoming rating 630A – 4000A+ 200A – 1600A
Outgoing feeders ACBs / MCCBs Contactor + overload units
Control devices None (distribution only) Contactors, relays, VFDs, PLCs
Downstream of Transformer / DG set PCC or sub-distribution board
Applicable standard IS 8623 / IEC 61439-1&2 IS 8623 / IEC 61439-1&2 + IEC 60947-4-1

When Do You Need Both?

In most medium to large industrial plants — a food processing unit, a water treatment plant, a textile mill — you need both a PCC and one or more MCCs. The PCC sits at the top of the LV distribution hierarchy. MCCs hang off it, each serving a group of motors or a process area.

A small plant with only a handful of motors might combine both functions into a single PCC-cum-MCC panel. This reduces cost and footprint but only works where the fault level and total connected load are modest enough that one enclosure can handle both roles safely.

Can a PCC and MCC Be in the Same Room?

Yes — in fact, they are almost always in the same electrical room or substation. The PCC is typically positioned near the incomer (transformer LV side or DG output), with MCCs arranged downstream. Cable management, busduct runs, and protection coordination are designed together.

PCC and MCC Panels — Built in Nashik by Chandrama Automation

At Chandrama Automation, we build both PCC and MCC panels from our facility in Ambad, Nashik. Our panels are assembled to IS 8623 and IEC 61439 standards, using components from Schneider Electric, L&T, Siemens, and ABB. We handle custom configurations — PCC-cum-MCC, intelligent MCCs with VFDs and PLCs, and remote I/O for distributed installations.