Why a Clear Specification Matters

A vague panel enquiry — "we need an MCC for 10 motors" — leads to vague quotations that cannot be compared. Each manufacturer fills in the unknowns differently, and the resulting quotes differ in scope rather than in price. When you award work on an incomplete spec, the gaps show up as variation orders during manufacturing or, worse, at site when the panel does not do what was needed.

A well-structured specification takes an hour to write and saves weeks of back-and-forth. Here is what to include.

1. Supply Voltage and System Parameters

State the supply clearly:

  • Voltage: typically 415V AC, 3-phase, 4-wire, 50 Hz in India
  • System fault level (prospective short-circuit current) at the panel incomer — e.g. 25 kA, 36 kA, or 50 kA for 1 second
  • Control voltage: 230V AC (single-phase from the main supply) or 24V DC from an internal SMPS — specify which
  • Whether a neutral is required for outgoing circuits

2. Incomer Details

Specify how the panel receives its supply:

  • Incomer type: ACB (Air Circuit Breaker) for high currents, MCCB (Moulded Case Circuit Breaker) for lower ratings
  • Incoming current rating (amps)
  • Whether a bus coupler is needed (for dual-incomer, auto-changeover arrangements)
  • Metering at the incomer: ammeter, voltmeter, kWh meter, power analyser

3. Outgoing Feeders

For each outgoing circuit, provide:

  • Circuit name and load description (e.g. "Pump P-101, 11 kW")
  • Motor/load kW and full-load amperes
  • Starting method: DOL, star-delta, soft starter, VFD
  • Control mode: local only, remote only, or local/remote selectable
  • Protection required: thermal overload, earth fault, phase failure relay
  • Whether indication lamps or mimic panels are needed

A motor schedule in spreadsheet format is the most efficient way to convey this. If you have a process flow diagram or P&ID, sharing it alongside the schedule gives the manufacturer useful context.

4. Construction Standard

State the applicable standard — IS 8623 / IEC 61439-1 & 2 is the norm for Indian industrial projects. Also specify:

  • Form of separation: Form 3b or Form 4 (see our article on IS/IEC standards)
  • IP rating of the enclosure: IP42 for clean indoor, IP54 for dusty or wet locations, IP55/IP65 for outdoor
  • Enclosure material: CRCA (Cold Rolled Close Annealed) steel is standard; stainless steel or GRP for corrosive environments
  • Colour: standard RAL 7035 light grey is typical; specify if different

5. Component Preferences

Many buyers and consultants specify preferred component makes. Common preferences for Indian projects:

  • Contactors and overloads: Schneider Electric, L&T, Siemens, ABB
  • MCBs and MCCBs: Schneider, L&T, Havells, ABB
  • ACBs: Schneider, Siemens, ABB
  • VFDs: ABB, Siemens, Danfoss, Schneider
  • Relays: Omron, Finder, Phoenix Contact

If the project has a preferred vendor list (PVL), include it. If not, state whether equivalent makes are acceptable and to what approval process.

6. Automation and Instrumentation

If the panel includes a PLC, specify:

  • PLC make and model preference, or leave open for manufacturer recommendation
  • Digital input count (from field switches, limit switches, motor feedback)
  • Digital output count (to contactors, solenoids, alarms)
  • Analogue inputs (from sensors: 4–20 mA, PT100, etc.)
  • Analogue outputs (to VFDs, control valves)
  • Communication protocol: Modbus RTU/TCP, Profibus, PROFINET, EtherNet/IP, BACnet

7. Physical Constraints

Mention any site constraints that affect the panel design:

  • Maximum available floor space or height restriction
  • Cable entry direction: top or bottom (bottom entry is more common in Indian installations)
  • Transportation constraints (door widths, crane limitations)
  • Whether the panel needs to be shipped in sections and assembled on site

8. Documentation Required

State what documentation you need with the panel:

  • Single-line diagram (SLD)
  • General arrangement (GA) drawing with dimensions
  • Control schematic and wiring diagram
  • Bill of materials (BOM) with make and model numbers
  • Factory acceptance test (FAT) report
  • O&M manual

If drawings need to be submitted for client or consultant approval before manufacturing starts, state the submission and approval timeline in your enquiry. This is the single biggest driver of manufacturing lead time on custom panels.

Sending the Enquiry

Compile the above into a single document or email. Attach the motor schedule, any drawings you have, and the project specification or tender document if applicable. The more complete your enquiry, the more accurate and comparable the quotation you receive.

At Chandrama Automation, we handle enquiries at all stages of specification — from a one-page sketch to a fully detailed tender document. If you are early in the process and need help structuring your specification, our engineers are available to assist.