The Two Standards You Will See on Panel Drawings
When an Indian electrical consultant or project manager specifies a control panel, the drawing will usually say "manufactured to IS 8623" or "manufactured to IEC 61439-1 & 2". These two standards are closely related — IS 8623 is the Indian Standard for low-voltage switchgear and control gear assemblies, and it largely adopts IEC 61439 (the international equivalent). Understanding both is straightforward once you see how they relate.
IS 8623: The Indian Standard
IS 8623 (Bureau of Indian Standards) covers the design, construction, and verification of low-voltage switchgear and control gear assemblies (LSCAs). It specifies requirements for:
- Electrical clearances and creepage distances between live parts
- Short-circuit withstand (rated short-time withstand current, Icw)
- Temperature-rise limits for busbars, terminals and components
- Degree of protection (IP rating) of the enclosure
- Busbar sizing, bracing and insulation
- Documentation requirements (single-line diagram, general arrangement, component list)
IS 8623 was revised to align with IEC 61439-1 (general rules) and IEC 61439-2 (power switchgear and control gear assemblies). For most industrial panels in India, IS 8623 is cited in purchase orders and tender specifications, but the technical requirements are functionally the same as IEC 61439.
IEC 61439: The International Framework
IEC 61439 is a multi-part standard. Part 1 covers general rules; Part 2 covers power switchgear and control gear assemblies (the most commonly applicable part for PCCs and MCCs). Other parts cover distribution boards for household use, motor control centres, and particular assemblies.
IEC 61439 introduced the concept of original manufacturer and assembly manufacturer. The original manufacturer (e.g. Schneider, Siemens, ABB) defines the type-tested assembly. The assembly manufacturer (a panel builder like Chandrama Automation) builds panels conforming to the original manufacturer's reference design. This distinction matters because the type tests (temperature rise, short circuit, etc.) are done on reference designs — not on every individual panel built to that design.
Form of Separation
Both IS 8623 and IEC 61439 define four "Forms" of internal separation within a panel. This tells you how functional units are separated from each other and from busbars:
| Form | What is separated | Typical use |
|---|---|---|
| Form 1 | No internal separation | Simple distribution boards |
| Form 2 | Busbars separated from functional units | Basic MCCs |
| Form 3 | Busbars + terminals separated from functional units | Industrial MCCs (Form 3b most common) |
| Form 4 | Full separation — each unit isolated from others | Critical plant, process industries |
Most industrial tender specifications call for Form 3b or Form 4. Form 4 allows a faulty unit to be worked on while the rest of the panel remains energised — an important consideration for continuous-process plants.
Short-Circuit Ratings
Every panel must be rated for the prospective short-circuit current at the point of installation. This is calculated from the transformer impedance and cable impedance. Common ratings you will see on Indian industrial projects are 25 kA, 36 kA, and 50 kA for 1 second (expressed as Icw). The panel's busbars, connections, and all components must be rated to withstand this fault current without damage.
Always confirm the system fault level with the utility or the project's electrical consultant before ordering a panel. Under-specified fault rating is a serious safety risk and a common source of specification errors.
What "Manufactured to IS 8623" Actually Means
When a panel builder says their panels are manufactured to IS 8623, it means they are following the standard's requirements in design and construction. It does not automatically mean the panel has been third-party certified or tested by BIS. For most industrial and commercial projects in India, compliance is verified by the consultant or buyer's inspection team rather than by BIS certification. However, for certain government and infrastructure projects, BIS or third-party test reports may be a contractual requirement.
Always ask your panel manufacturer which aspects of the standard they verify by calculation or test, and request the relevant documentation.
IS 8623 / IEC 61439 Compliance at Chandrama Automation
Our panels are designed and built to IS 8623 / IEC 61439-1 & 2. We use type-tested systems from Schneider Electric (Prisma iPM, Okken), L&T (MCC systems), and other approved manufacturers as the reference design base. Our documentation package includes single-line diagrams, general arrangement drawings, component schedules, and test reports. We are happy to discuss specific standard requirements with consultants and buyers at the design stage.